6. Parameters of the initial mode-1 8.1
6.1. Operation mode with nominal power.
Assume that the generator operates into an infinite busbar
system. All values are in per-unit system (index ✱ is omitted).
Active stator resistance is neglected.
6.1.1. Active generator current
Iг0  =  Iн  =  1
6.1.2. Total generator current
Ia0  = 
1
cosφн
 = 
1
0.9
 =  1.11
6.1.3. Angle between the voltage vector on the TG busses (Ua) and total current (Ia)
φ0  =  arccos 0.9  =  -25° (lagging)
6.1.4. Reactive generator current
Ix0  =  Ia0  ·  sinφ0  =  1.11  ·  sin(-25°)  =  1.11  ·  (-0.42)  =  -0.47
6.1.5. Angle between axis q and voltage on generator busses (δ-β). δ - angle between
axis q and fixed axis, β - angle between voltage vector and fixed axis.