The transfer function of the open-loop voltage control loop under
the rated load condition |
22.2
|
|
|
At ΔUтн = 100 V,
Uвыпр = 44.6 V.
Kвх-u= 44.6/100 ·2/4
Kтн = 100 / 24000 ; Ub = 24000/√3
By definition:
ΔUa* p.u. -
generator terminal phase voltage increment, so
KТН=ΔUтн/ΔUа✱=100 /√3) ;
Kосu = (44.6 / 100) ·(2/4)·(100/√3) = 12.
Total feedback regarding voltage and reactive current.
Using the LAFC diagrams (Fig. 11):
Gосu,р(p) = Kосu
+ Gоср(p)
= 12 · (1 + p · 0.003).
The transfer function of the open-loop voltage control loop under
the rated load condition (From Fig. 9.d):
|
|
Gкн.р(p) = GБн(p) · Gэв(p) · G5
· GГ(p) · Gоси,р(p) |
|
|
Below are the formulas and calculations for all
components of the voltage control loop open-loop transfer function,
along with references to the pages where specific calculations and
explanations are provided. |
|
for GБН(p)
- pages 9.2; (19.1 - 20): |
|
|
= |
|
0.52·(1+p·0.156)·(1+p·0.5) |
| (1+p·0.6)·(1+p·0.03) 2 |
|
|
|
|
|
|
|
G5 = 885 (page 12.1) |
|
Gг(p)
|
=
|
|
|
(pages 14.3; 14.6) |
|
|
Gоси,р(p) = 12 · (1 + p
· 0.003) (see the above) |
|
|