The transfer function of the open-loop voltage control loop under the rated load condition 22.2

At ΔUтн = 100 V,
Uвыпр = 44.6 V.
Kвх-u= 44.6/100 ·2/4
Kтн = 100 / 24000 ; Ub = 24000/√3  By definition: ΔUa* p.u. - generator terminal phase voltage increment, so
KТН=ΔUтн/ΔUа✱=100 /√3) ; Kосu = (44.6 / 100) ·(2/4)·(100/√3) = 12. Total feedback regarding voltage and reactive current.
Using the LAFC diagrams (Fig. 11):
Gосu,р(p) = Kосu + Gоср(p) = 12 · (1 + p · 0.003).

The transfer function of the open-loop voltage control loop under the rated load condition (From Fig. 9.d):

Gкн.р(p) = GБн(p) · Gэв(p) · G5 · GГ(p) · Gоси,р(p)

Below are the formulas and calculations for all components of the voltage control loop open-loop transfer function, along with references to the pages where specific calculations and explanations are provided.

for GБН(p) - pages 9.2; (19.1 - 20):

GБН(p)

 =   
ΔU5
ΔU1
 ·  <
ΔU6
ΔU5
=
0.52·(1+p·0.156)·(1+p·0.5)
(1+p·0.6)·(1+p·0.03) 2
 

Gзв(p)

=

0.052
(1 + p · 0.0047)
 

( page 21.3)

 

G5 = 885 (page 12.1)

Gг(p)

=

0.11
1 + p·2.4

 

(pages 14.3; 14.6)

Gоси,р(p) = 12 · (1 + p · 0.003) (see the above)