20

ΔU6
ΔU5
 ≈
0.13 · (1 + p · 0.5)
(1 + p · 0.03)2
GБН(p) = 
ΔU5
ΔU1
 · 
ΔU6
ΔU5
 =
= 
4 · (1 + p · 0.156) · e-p · 0.0053
1 + p · 0.6
 · 
0.13 · (1 + p · 0.5)
(1 + p · 0.03)2
KБН = 4 · 0.13 = 0.52

7.7. Reactive Current Sensor (DRT) -see fig.9b at the page 21.2
According to adjustment data:
Ia = 0;  Ir = Irн = 21400 · 0.425 = 9100 A
Current transformer ratio  Kт = 
5
24000
At Iрн  CT output current:  
5·9100
24000
 = 1.94 A    KДРТ = KДРТ1 +   KДРТ2
At 1.94A DRT output voltage: 5 V        KДРТ2 = 5/1.94 V/A
KДРТ1 = 1.94/0.425 A/p.u

In per -units system:

 Iрн*   =
Irн
Iб

=

9100
21400

=

0.425

p.u
ΔUДРТ
ΔIр✱
=  KДРТ

=

5
1.94
  ·
1.94
0.425
=  11.7 V/p.u
ΔUДРТ -to Input node to amplifier Д3 in unit БН (page 22.1)