| 7.1 Structural diagram of a turbogenerator |
10.1 |
|
The structural diagram of a turbogenerator in load mode is shown in Fig. 4. A linearized system of equations [L1] is taken as the basis.
|
|
|
| ΔMЭ✱ |
= |
K1 |
· |
Δδ |
+ |
K2 |
· |
E′q✱ |
|
| ΔUа✱ |
= |
K5 |
· |
Δδ |
+ |
K6 |
· |
ΔE′q✱ |
|
|
|
|
Torque is expressed in per-unit (p.u.) based on the three-phase power rating, and the d/dt operator is replaced by p. Symbol definitions are provided in Fig. 4.
|
|
Main assumptions: neglecting magnetic circuit saturation, stator active resistance, and the influence of damper windings; assuming operation into an infinite bus system.
|
7.1.1 Transfer function of Gв(p) element
We derive it from the relation:
Ef = if · Rв + Lв ·p ·if
Rв and Lв - resistance and inductance of the excitation circuit.
In per-unit system (relative units):
|
if✱ ·ifб
·Rf✱ ·Rfб |
| Ef✱ · Ufб |
|
= |
|